1、DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT by Philip J. A. Ling, P.Eng. Cyril J. Eldridge, B. Sc. POWERSMITHS INTERNATIONAL CORP 416-

2、439-1077 ABSTRACT Generally, the electrical community has come to accept the fact that today's office facilities have an abundance of electronic equipment that produce harmonics. Based on the results of hundreds of electrical system surveys we have determined that the predominant harmonics are t

3、riplens; however, a high degree of 5th and 7th harmonics are also present and need to be treated for a more comprehensive solution. These harmonic rich environments are known to cause serious operational problems for users as well as building maintenance personnel. Until recently, no cost- effec

4、tive methods have been proposed that can universally deal with 3rd, 5th and 7th harmonics during the design and specification stage of three phase four wire electrical distribution systems. By integrating phase shifting into an extremely low zero phase sequence impedance transformer with single o

5、r multiple outputs, substantial reduction of triplen, 5th and 7th harmonics can be achieved. The net result is that the electrical distribution system predictably becomes electromagnetically compatible with the electronic loads (e.g. personal computers) it has to supply. 1. INTRODUCTION Traditi

6、onal electrical system design had very little need to deal with harmonics because the loads typically designed for were linear in nature. Over the years, as more and more research and practical experience was gathered with linear loads, the design process became more and more predictable. With th

7、e proliferation of variable speed drives, electronic ballasts, personal computers and other electronic equipment, electrical system design strategies need to be adjusted. Because in many cases a major portion of the loads today are nonlinear in nature, the loading due to harmonics created by thes

8、e loads must also be taken into consideration. While this seems to be a reasonable request , you might ask just how does one predict these new loading requirements and plan for them. Over the years, essentially two approaches evolved and became widely used to address harmonics . Phase-shifting t

9、ransformers of different configurations , used for decades in industrial and computer facilities, typically treat harmonics produced by loads that are balanced and connected phase to phase e.g. 5th, 7th, 11th, 13th harmonics. Zero sequence filters (zig-zag reactors, etc.) have been used in commer

10、cial and institutional settings to address triplen harmonics (3, 9, 15 …...) and associated problems (high neutral current, voltage distortion, etc.). Designing next generation electrical systems The evolution of electronic power supplies (switch-mode) has generated the need for a solution enc

11、ompassing the benefits of both previous approaches. While the 5th & 7th harmonics are present and require treatment, the predominant harmonic is the 3rd, which not only causes high neutral current and neutral-to-ground voltage, but just as importantly causes a substantial increase in voltage dist

12、ortion which, as a whole, is more frequently problematic for electronic equipment. This paper describes how Symmetrical Components Theory has been used to design a completely new and innovative transformer that integrates the treatment of zero sequence harmonics (triplen etc.) as well as 5th & 7t

13、h harmonics. These transformers may be configured as single or multiple output units to accommodate various design strategies. Besides taking the guess work out of the design process, these transformers can be included at the base building design stage in a similar way that traditional transforme

14、rs would be allocated. This approach, in the majority of cases, eliminates the need for remedial equipment to be added later when problems are already occurring. Case studies of actual distribution systems are presented that document the effectiveness of this approach. 2. BACKGROUND Until the m

15、id-1980’s, there was essentially no significant harmonic-generating equipment in commercial or institutional buildings. As a result, standard practices for electrical system design were appropriate and the biggest concern was maintaining the requisite Power Factor, which could be achieved by addi

16、ng a capacitor bank of the necessary kVAR. From the point of view of harmonics, these buildings were basically trouble-free: no unusually hot transformers or neutral conductors, few voltage distortion problems, and infrequent cases of resonance or capacitor bank overloading. The decade of the ei

17、ghties brought digital electronics and the personal computer age. The arrival of these radically new types of loads has meant problems of a magnitude that no one imagined. The consumption of these new (nonlinear) loads is far from the ideal sinusoidal waveform (linear) that power systems were des

18、igned to feed and the result is serious harmonic problems. This paper will focus on the impact of the Personal Computer (PC) and similar electronic equipment on power distribution systems. The PC and PC-based workstations are moving rapidly into the workplace everywhere - from the office having t

19、raditionally little load, to computer rooms used to phase-phase and 3-phase loads. Another good example of where electronic loads dominate the load profile is broadcast facilities. A few special notes should be made about this type of equipment. It is connected phase-neutral (120V), which means

20、that the neutral conductors in the system are part of the current circuit. Whereas phase-phase (208V) load harmonic spectrums are rich in 5th, 7th, 11th and 13th harmonics, the 120V, phase-neutral PC draws a pulsed current with a rich harmonic spectrum dominated by the 3rd harmonic and with appre

21、ciable levels of 5th and in many cases 7th harmonics. While it has been associated for many years with causing high neutral current and hot transformers [1,2] , the same PC that is the source of the current harmonics, is itself sensitive to voltage distortion that results. In our experience, the

22、costs associated with downtime far exceed all other costs, yet they are the most difficult to measure. The relevant North American standard POWERSMITHS INTERNATIONAL CORP page 2 Designing next generation electrical systems [3] IEEE-519-1992 “Recommended Practice …” specifically singles out el

23、ectronic equipment (section 6.6) and highlights its sensitivity to distortion of the supply voltage waveform listing consequences of excessive distortion such as erratic equipment malfunction and premature failure. Recommended limits are set at 5% Total Harmonic Distortion (THD) with no individua

24、l harmonic exceeding 3% of the fundamental. It is clearly undesirable to be in a position of having to design a system knowing it feeds a PC-rich environment, acknowledging that this means a harmonic-rich environment and therefore potentially a problem-rich environment. However, you still resign

25、 yourself to waiting until the client is moved-in, operating, and experiencing problems (complains) before attempting to treat the harmonics because existing approaches require accurate information about load conditions and details of the specific harmonic spectrum at hand. What is required is a

26、n approach that can not only tackle the harmonics successfully, but that can be applied at the design stage so that remedial action is very rarely required. 3. WHICH HARMONICS TO DESIGN FOR The first step towards preemptively solving a harmonic problem is to develop a typical “fingerprint” of th

27、e expected loads. It is important to note that some environments have more stable loads than others and there can also be quite a diversity of equipment connected to the same system. Also, in time the loads and their harmonic content could change. These reasons have been cited as evidence that it

28、 is not practical to quantify potential harmonic problems unless the load is well-defined and stable. While acknowledging that it is difficult to anticipate the precise magnitude of the different harmonics beforehand especially where loading varies significantly, it is possible to provide success

29、ful, off-the-shelf harmonic treatment by predicting the types of harmonics rather than trying to quantify each. In the course of our research, we conducted and reviewed extensive field data with respect to the current spectrum of loads in commercial, institutional and industrial settings. What em

30、erged were consistent load profiles; these findings are perhaps surprisingly simple. There are two basic load profiles - one typical of phase-neutral loads and another typical of phase-phase and 3-phase loads (see figure 1). POWERSMITHS INTERNATIONAL CORP page 3 Designing next generation ele

31、ctrical systems The results can be summarized as follows: 1. Where there are phase-neutral loads, a rich harmonic current spectrum can be expected comprising mainly of 3rd, 5th & 7th harmonics with the 3rd being predominant yet the 5th and sometimes 7th being troublesome. 2.

32、 As expected, where phase-neutral loads were in the majority, neutral current exceeded the phase current by a wide margin, 1.5 times on average. The data we have compiled over the past several years shows a clear tendency for the level of neutral current to increase relative

33、to the phases. Two years ago it was common to find neutral current about equal to phase current. We have recently measured several sites at 2.2 times! 3. Phase-phase and 3-phase loads show a predominance of 5th & 7th harmonics with a noted absence of 3rd harmonic. There is no neu

34、tral current since the neutral is not part of their circuit. 4. While there were instances of 11th & 13th harmonics dominating the spectrum (12-pulse UPS & drives) they were far less in overall proportion and were in very localized systems. These are the commonly found electrica

35、l loads in our facilities today. Personal Computer 208V Power Supply VFD or UPS What we can summarize from this information is that the harmonic spectrums were consistent, predictable, and dominated by only 3 harmonics: the 3rd, 5th & 7th. Neutral current is present and requires attention wher

36、e there are phase-neutral loads. The authors also reviewed historical data to see whether the continuing advances in switch-mode power supply technology were having an impact on the current spectrum. There is indeed a trend to higher harmonic levels. The harmonic spectrum is similar except that a

37、ll harmonics tend to get higher as a percent of the fundamental. The 9th harmonic in some cases is high enough to warrant treatment (the 9th adds in the neutral conductor similar to the 3rd). POWERSMITHS INTERNATIONAL CORP page 4 Designing next generation electrical systems 4. THEORETICAL BA

38、SIS FOR TREATMENT OF PROBLEM HARMONICS When trying to resolve any problem, clear identification of the goal is of prime importance since both the effectiveness and cost of the treatment are at stake. Our objectives can be listed as followed: 1. Reduce voltage harmonic levels to within limits

39、 set out in IEEE-519-1992 (5% THD voltage with no individual harmonic above 3%). 2. Ensure the transformer and cables are not overloaded. 3. Use passive approach for simplicity, highest reliability, lowest maintenance, lowest cost. 4. Avoid the use of capacitors (risk of reson

40、ance, etc.). When dealing with harmonics it is important to understand the relationship between current harmonics and voltage harmonics. Current harmonics in themselves cause extra heating in electrical components through which they flow, namely transformers and cables. However, their effect can

41、 be more widespread. Because they flow through the system impedance, current harmonics create voltage drops at their respective harmonic frequencies, distorting the voltage waveform, which in turn affects other equipment connected to the system (see figure 3). The term used when discussing the in

42、teraction of equipment is “electromagnetic compatibility”. Figure 3: How Harmonic Currents Create Voltage Distortion Vthd 1 Vt hd 2 Z1 Z2 Vthd 3 Z3 Vt hd 4 Vthd 5 Z4 Z5 Vt hd 6 Z6 Vthd Sourc e Zs ource Ih V h= I h x Z h E QUI P ME NT Vt hd LoadHa rmo nic cur r

43、e nt sou rce Where: Vh Ih Zh (Ohm's Law) h th harmonic voltage h th harmonic current system impedance for h th harmonic Figure 3 makes it very clear that in the treatment of voltage harmonic distortion, one can either reduce the magnitude of the harmonic current or the system impedanc

44、e at the frequencies that harmonic currents are present, or both. POWERSMITHS INTERNATIONAL CORP page 5 Designing next generation electrical systems From a design point of view, there is a load requirement and provision must be made for that certain kVA of load. Although at the outset the ex

45、act profile of the load is generally not known, certain information is available. The local environment will be one of three configurations: all phase-neutral, all phase-phase or 3-phase, or a mixture of both types of loads. In terms of approach to treatment, the mixed case should be treated the

46、same way as if the loads were all phase-neutral. The harmonic currents to be expected are as per our previous discussion, and the harmonics to be treated are either 3rd, 5th, 7th & neutral current for phase-neutral loads, or 5th & 7th for phase-phase and 3-phase loads. If 12-pulse systems are use

47、d, 11th & 13th harmonics are predominant. Symmetrical components & 2 families of harmonics An in-depth treatment of Symmetrical Components Theory is beyond the scope of this paper, but it needs to be touched upon in order to understand the basis upon which harmonics can be treated. In the earl

48、y part of this century, an Engineer named Fortesque [4] developed a method by which any system of 3 unbalanced vectors can be represented by a set of 3 balanced systems of vectors which he called positive, negative and zero sequence components (see figure 4). Figure 4: Example of Symmetrical Comp

49、onents A A+ rotation A0 A- B- C- rotation = C B C+ B+ P os it iv e S eq ue nc e U n ba la nc e d 3- Ph a se Sy s t e m + + B0 C0 N e ga t iv e S eq ue nc e Z e ro S eq ue nc e The following chart shows the harmonic sequence based on Symmetrical Components Theory.

50、 1234567etc.Harmonic (fund.) Sequence + - 0 + - 0 + Note: unbalanced portions of positive & negative sequence currents are also zero phase sequence in nature and appear in the neutral. For example the unbalanced portion of 60Hz that flows back in the neutra

51、l is zero sequence. The conversion involves complex mathematical manipulation, but what needs to be remembered in our application is the behavior of the different symmetrical components with respect to transformers and cables. First of all, by their nature positive and negative sequence currents

52、flow through transformers from the secondary into the primary system. POWERSMITHS INTERNATIONAL CORP page 6 Designing next generation electrical systems Zero Sequence Components Zero sequence currents are important for several reasons: ? they flow only in 3-phase, 4-wire systems, and becaus

53、e they are in phase in all three phases, they add together in the neutral conductor ? they are trapped circulating in the transformer primary delta windings causing additional heating ? they flow through the system impedance causing voltage distortion Zero sequence impedance is of particu

54、lar importance: ? zero sequence impedance of a delta-wye transformer is equal to its positive and negative sequence impedance (the nameplate value). This is important because the overwhelming majority of distribution transformers have this type of connection, which means the delta-wye t

55、ransformer is a reasonably high impedance for 3rd harmonic current thus contributing significantly to high voltage distortion at 3rd harmonic (remember Ohm’s law). ? zero sequence impedance of a cable can be several times higher than its positive and negative sequence values or at least equ

56、al to them. This means that any significant cable run feeding phase-neutral loads will result in high 3rd harmonic voltage distortion at these loads. Neutral to ground voltage, sometimes referred to as common mode noise, is a direct product of the neutral current and zero phase sequence impeda

57、nce of the cables. The notion of symmetrical components is important because all currents of the same type behave in the same way. A zig-zag reactor treats high neutral current on the basis that it is a zero sequence filter by its nature and since all currents flowing on the neutral are zero sequ

58、ence, the approach works. This approach is now widely used for removing neutral current. The zero sequence network and the behavior of zero sequence currents is key because the predominant harmonic in phase-neutral loads - the 3rd harmonic, is zero sequence, therefore low zero sequence impedance

59、 is vital to the overall success of any complete treatment involving phase-neutral loads. Remember that because they are all in the same family, any modification of the zero sequence network affects all zero sequence currents (3,9,15… & unbalanced portions of others). Positive & Negative Sequenc

60、e Components Understanding of positive & negative sequence currents is key to resolving the other harmonics we have identified as needing to be treated - the 5th & 7th. As noted in the above table, 5th is negative sequence and 7th is positive sequence in nature. The fact that they both flow throu

61、gh transformers and yet rotate in opposite direction allows us to use one phase-shift to remove pairs of positive and negative sequence harmonics from two separate sources. The case we are most interested in is the 30° phase-shift between two similar harmonic sources. As figure 5 illustrates, th

62、e phase sequence difference results in cancellation of both 5th & 7th harmonics (the result is the same for 17th & 19th etc. as well). This method has been used for decades in aluminum and electrochemical industries by using secondary phase shifted transformer windings to supply heavy non-linear

63、rectifier loads. POWERSMITHS INTERNATIONAL CORP page 7 Designing next generation electrical systems Figure 5: How a 30° phase-shift between 2 sources result in cancellation of both 5th & 7th harmonic currents A: No Shift B: 30° Shift A 7 A 5 30° B 7 =

64、 7 x 30° = 210° counter-clockwise (7th is positive sequence) B 7 B 5 B 5 = 5 x 30° = 150° clockwise (5th is negative sequence) RESULT: 5th harmonic in 7th harmonic in A opposes 5th in A opposes 7th in B B 5. Inherently Treating Problem Harmonics Because of the direct re

65、lationship between harmonic current and system impedance in the creation of voltage distortion, it is clear that the location of highest voltage distortion will be at the harmonic-producing loads themselves - at the deepest point of your distribution system. Figure 6 illustrates the impact of sys

66、tem components like transformers and cables as well as load on voltage distortion. It is the combination of high zero sequence impedance of the components and high levels of 3rd harmonic current (which is zero sequence in nature) that causes a dramatic increase in 3rd harmonic distortion at various points. The figure also illustrates that it is true that the transformer has blocked the zero sequence currents from flowing upstream, but at the expense of a substantial increase in voltage dist

展開閱讀全文
溫馨提示:
1: 本站所有資源如無特殊說明,都需要本地電腦安裝OFFICE2007和PDF閱讀器。圖紙軟件為CAD,CAXA,PROE,UG,SolidWorks等.壓縮文件請(qǐng)下載最新的WinRAR軟件解壓。
2: 本站的文檔不包含任何第三方提供的附件圖紙等,如果需要附件,請(qǐng)聯(lián)系上傳者。文件的所有權(quán)益歸上傳用戶所有。
3.本站RAR壓縮包中若帶圖紙,網(wǎng)頁內(nèi)容里面會(huì)有圖紙預(yù)覽,若沒有圖紙預(yù)覽就沒有圖紙。
4. 未經(jīng)權(quán)益所有人同意不得將文件中的內(nèi)容挪作商業(yè)或盈利用途。
5. 裝配圖網(wǎng)僅提供信息存儲(chǔ)空間,僅對(duì)用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對(duì)用戶上傳分享的文檔內(nèi)容本身不做任何修改或編輯,并不能對(duì)任何下載內(nèi)容負(fù)責(zé)。
6. 下載文件中如有侵權(quán)或不適當(dāng)內(nèi)容,請(qǐng)與我們聯(lián)系,我們立即糾正。
7. 本站不保證下載資源的準(zhǔn)確性、安全性和完整性, 同時(shí)也不承擔(dān)用戶因使用這些下載資源對(duì)自己和他人造成任何形式的傷害或損失。

相關(guān)資源

更多
正為您匹配相似的精品文檔
關(guān)于我們 - 網(wǎng)站聲明 - 網(wǎng)站地圖 - 資源地圖 - 友情鏈接 - 網(wǎng)站客服 - 聯(lián)系我們

copyright@ 2023-2025  zhuangpeitu.com 裝配圖網(wǎng)版權(quán)所有   聯(lián)系電話:18123376007

備案號(hào):ICP2024067431號(hào)-1 川公網(wǎng)安備51140202000466號(hào)


本站為文檔C2C交易模式,即用戶上傳的文檔直接被用戶下載,本站只是中間服務(wù)平臺(tái),本站所有文檔下載所得的收益歸上傳人(含作者)所有。裝配圖網(wǎng)僅提供信息存儲(chǔ)空間,僅對(duì)用戶上傳內(nèi)容的表現(xiàn)方式做保護(hù)處理,對(duì)上載內(nèi)容本身不做任何修改或編輯。若文檔所含內(nèi)容侵犯了您的版權(quán)或隱私,請(qǐng)立即通知裝配圖網(wǎng),我們立即給予刪除!